    Wastewater Treatment

    Failure Analysis of Lined Reinforced Polyvinylidene Fluoride Hollow Fiber Curtain Membrane Casing (MBR Casing)

    MBR System Fault Diagnosis and Troubleshooting Table

    FaultPossible CausesWorkaround
    The suction pump cannot pump out waterSuction pump reverseAdjust the wiring of the suction pump to make it rotate forward

    There is no water in the suction pump cavityFill the suction pump cavity with water before starting

    The suction pump inlet pipeline is seriously leakingFind and repair leaks
    The water contains a lot of bubblesThe suction pump inlet pipe is leakingFind and repair leaks
    Insufficient or uneven aerationBlower failureFind and correct the cause of the fault, repair or replace the blower

    Internal and external aeration pipes are blockedFind and correct the cause of blockage, clean or replace the internal and external aeration pipes
    The water flow rate decreases or the transmembrane pressure difference rises too quicklyGrease and mineral oil, etc. MBR membrane blocked by dirtFind and correct the cause of fouling and blockage, clean or replace the MBR membrane

    Defoaming agents, coagulants and flocculants, etc. MBR membrane blocked by dirtFind and correct the cause of fouling and blockage, clean or replace the MBR membrane

    MBR pool water temperature is lowIncrease water temperature according to design requirements

    Sludge concentration is too lowIncrease sludge concentration according to design requirements

    Sludge concentration is too highReduce sludge concentration according to design requirements

    Poor sludge settling performanceImprove sludge settling performance according to design requirements

    High sludge viscosityReduce sludge viscosity according to design requirements
    The water is turbid or the water quality is poorPretreatment failedEnsure pretreatment is qualified according to design requirements

    Bacteria growing inside the MBR membraneSterilization of MBR membranes

    Bacteria growing inside the outlet pipeSterilize the water outlet pipe

    Damaged water collection pipeFind and correct the cause of damage, repair or replace the water collection pipe

    Quick-release connector damagedFind and correct the cause of damage, repair or replace the quick connector

    Transparent hose is damagedFind and correct the cause of damage, repair or replace the transparent hose

    MBR membrane damageFind and correct the cause of damage, repair or replace the MBR membrane


    Notice! If you have any other problems, please consult our company's relevant technical personnel.